Boundary wall fire check

A house wall less than 900 mm from a side or rear boundary, or less than 1.8 m from another building on the lot, has to be fire-resisting. Enter the distance and see what applies to the wall, its openings and the eaves.

boundary450900no fire rating needed450900
Clause
9.2.1
Code
NCC 2022
Drawn in
mm
Pass1 of 1 check within limits
What the wall faces

A boundary with a road or other public space does not count. Nor does a shed or garage that belongs to the house.

mm

Measured square off the boundary, or off the other building's wall.

mm

Wall face to the outer edge of the eaves. Leave out a non-combustible fascia and gutter.

Checks

Pass. 1 of 1 check within limits.

  • Fire-resisting wall: For information.

    Not needed

    900 mm or more away9.2.1

  • Eaves edge: Within the limit.

    450 mm away

    450 mm or more, and non-combustible9.2.9(4)

  • Fascia, gutter, downpipes: For information.

    Non-combustible: any distance

    combustible: 450 mm or more away9.2.9

This checks the deemed-to-satisfy dimensions for houses (Class 1 and Class 10 buildings) in NCC 2022. State variations and your approved plans come first, and your certifier has the final say.

What the code asks for

  • A house wall less than 900 mm from a side or rear boundary has to be fire-resisting, and the openings in it protected. 9.2.1
  • The same applies to a wall less than 1.8 m from another building on the same lot. A shed or garage that belongs to the house does not count. 9.2.1
  • A boundary with a road or other public space does not count. 9.2.1
  • The distance is measured at right angles to the boundary, and only the part of the wall inside it needs protecting. 9.2.2
  • The wall has an FRL of at least 60/60/60 tested from the outside, or is masonry or masonry veneer at least 90 mm thick. 9.2.3(2)
  • It starts at the footings or slab and runs to the underside of a non-combustible roof covering or non-combustible eaves lining. 9.2.3(1)
  • Openings in it are fire windows that do not open, with an FRL of -/60/-, or self-closing solid core doors at least 35 mm thick. 9.2.3(3)
  • Eaves with non-combustible roofing and lining, and combustible fascias, gutters and downpipes, come no closer than 450 mm to the boundary or 900 mm to the other building. 9.2.9(4)
  • Non-combustible fascias, gutters and downpipes can sit inside those distances. 9.2.9(3)
  • South Australia also treats a brush fence within 3 m of the wall the same way. SA 9.2.1

Source: Part 9.2 of the ABCB Housing Provisions (NCC 2022). The distances and the wall and opening requirements are the same in NCC 2025.

Questions people ask

How close to the boundary can I build a house?

This part of the NCC does not set a setback. It says a wall less than 900 mm from a side or rear boundary has to be fire-resisting. Setbacks come from your council and state planning rules, which are separate.

Can I have a window in a wall near the boundary?

Inside 900 mm it has to be a fire window that does not open. There is one exemption for non-habitable rooms, where the window is at least 600 mm from the boundary or 1.2 m from another building on the lot. In a bathroom, laundry or toilet it can be up to 1.2 m². In other non-habitable rooms it can be up to 0.54 m² and has to be fixed, steel-framed wired glass or hollow glass blocks.

How close can eaves and gutters come to the boundary?

Eaves with non-combustible roofing and lining can come to 450 mm from the boundary and no closer. Combustible fascias, gutters and downpipes have the same 450 mm limit. Non-combustible ones can sit closer.

Does a garage or carport near the boundary need a fire wall?

Often, yes. A garage or shed between the house and the boundary has to protect the house in one of the ways the code sets out, usually by sitting 900 mm or more off the boundary or by having a fire-resisting wall. An open carport can be exempt. See clauses 9.2.4 to 9.2.8.