Build to Code

All checks Housing Provisions 9.5.2

Smoke alarm location check

A house needs a smoke alarm in every hallway that serves bedrooms and on every other storey. Enter your layout to see how many that makes, and check where they are fixed.

bedrooms300need 1fitted 1
Clause
9.5.2
Code
NCC 2022
Drawn in
mm
Pass3 of 3 checks within limits
Storeys
1

Storeys with bedrooms
1

Bedroom hallways
1

Each hallway that serves bedrooms. Where bedrooms open straight off a living area, count that area.

Alarms fitted
1

Fixed to
mm

On a ceiling, out from the wall. On a wall, down from the ceiling.

Checks

Pass. 3 of 3 checks within limits.

  • Number of alarms: Within the limit.

    1

    1 or more9.5.2

  • Mains powered: Within the limit.

    Yes

    where mains power is supplied9.5.1

  • Interconnected: For information.

    Not needed

    only with more than one alarm9.5.1

  • Distance from the wall: Within the limit.

    300 mm

    300 mm or more9.5.4(a)

This checks the deemed-to-satisfy dimensions for houses (Class 1 and Class 10 buildings) in NCC 2022. State variations and your approved plans come first, and your certifier has the final say.

What the code asks for

  • On a storey with bedrooms, an alarm goes in every corridor or hallway that serves a bedroom. Where there is no hallway, it goes between the bedrooms and the rest of the house. 9.5.2(a)
  • Every other storey gets an alarm too, even with no bedrooms on it. 9.5.2(b)
  • Alarms comply with AS 3786 and are powered from the mains where the building has mains power. 9.5.1
  • Where there is more than one alarm, they are interconnected. 9.5.1
  • On a ceiling, an alarm sits at least 300 mm from the corner where the wall meets the ceiling. 9.5.4(a)
  • On a sloping ceiling, it sits between 500 and 1500 mm from the high point or apex. 9.5.4(a)
  • Where the ceiling is not possible, an alarm can go on a wall, between 300 and 500 mm below the ceiling. 9.5.4(b)
  • In a private garage where a smoke alarm would give false alarms, another kind of alarm allowed by AS 1670.1 can be used, as long as the rest of the house has AS 3786 smoke alarms. 9.5.1
  • Small boarding houses and guest houses (Class 1b) need more: an alarm in every bedroom, and lighting the alarm switches on to help people get out. 9.5.3, 9.5.5

Source: Part 9.5 of the ABCB Housing Provisions (NCC 2022). The smoke alarm rules are the same in NCC 2025.

Questions people ask

How many smoke alarms does a house need?

One in each hallway that serves bedrooms, and one on every storey that has no bedrooms. A single storey house with all its bedrooms off one hallway needs one. A two storey house with the bedrooms upstairs off one hallway needs two.

Do smoke alarms have to be hard wired?

Yes, where the house has mains power. And where there is more than one alarm they have to be interconnected, so that when one sounds they all do.

Does my state ask for more?

It can. New South Wales varies this clause, and states have their own smoke alarm laws for existing homes and rentals. Some ask for alarms inside bedrooms as well. Check your state's rules as well as the code.

Related checks