All checks Housing Provisions 10.8.2
Exhaust fan check
An exhaust fan has to move 25 L/s in a bathroom or toilet and 40 L/s in a kitchen or laundry, send it outside and let replacement air in. Pick the room and enter the fan to check all three.
- Clause
- 10.8.2
- Code
- NCC 2022
- Drawn in
- mm
Checks
Pass. 4 of 4 checks within limits.
Fan flow rate: Within the limit.
25 L/s
25 L/s or more10.8.2(1)
Discharges outside: Within the limit.
Yes
direct, or by duct or shaft10.8.2(2)
Make-up air under the door: Within the limit.
14,400 mm²
14,000 mm² or more10.8.2(5)
Light switch and run-on timer: Within the limit.
Yes
10 minutes after lights off10.8.2(4)
This checks the deemed-to-satisfy dimensions for houses (Class 1 and Class 10 buildings) in NCC 2022. State variations and your approved plans come first, and your certifier has the final say.
What the code asks for
- A fan in a bathroom or toilet moves at least 25 litres a second. A fan in a kitchen or laundry moves at least 40. 10.8.2(1)
- Exhaust from a kitchen, range hood, bathroom, toilet or laundry discharges to outdoor air, directly or through a duct or shaft. 10.8.2(2)
- A venting clothes dryer discharges to outdoor air the same way. 10.8.2(3)
- In a bathroom or toilet with no natural ventilation, a fan that does not run all the time is wired to the light switch and keeps running for 10 minutes after the light goes off. 10.8.2(4)
- A room with an exhaust fan and no natural ventilation needs make-up air: an opening to the next room with a free area of 14,000 mm², or one sized to AS 1668.2. 10.8.2(5)
- A 20 mm gap under a 700 mm wide door gives 14,000 mm². 10.8.2
- Natural ventilation here means windows or doors that open to at least 5% of the floor area. 10.6.2(a)
Source: Part 10.8 of the ABCB Housing Provisions (NCC 2022). The exhaust fan rules are the same in NCC 2025. Other parts of the condensation rules changed, so read Part 10.8 of the 2025 text if your job is under it.
Questions people ask
Can a bathroom fan vent into the roof space?
No. The exhaust has to discharge to outdoor air, either directly or through a duct or shaft.
What size exhaust fan does a bathroom need?
One that moves at least 25 litres a second. Fans are often rated in cubic metres an hour: 25 L/s is 90 m³/h, and 40 L/s is 144 m³/h.
Does the fan need a timer?
Only in a bathroom or toilet with no window or door giving natural ventilation, and only if the fan does not run all the time. Then it has to come on with the light and run on for 10 minutes.