Stair riser and going check

House stairs need risers of 115 to 190 mm and goings of 240 to 355 mm, with twice the riser plus the going between 550 and 700 mm. Enter your floor to floor rise and going to check a flight.

27403750R 171.3G 2502R + G = 592.516 risers
Clause
11.2.2
Code
NCC 2022
Drawn in
mm
Pass4 of 4 checks within limits
Stair type

Attic or store means a stair to a room that is not used daily.

mm

Finished floor to finished floor. With a landing part way, check each flight on its own.

mm

Nosing to nosing, measured level.

Risers
16

Auto aims for a riser close to 175 mm.

Checks

Pass. 4 of 4 checks within limits.

  • Riser height: Within the limit.

    171.3 mm

    115 to 190 mm11.2.2

  • Going: Within the limit.

    250 mm

    240 to 355 mm11.2.2

  • 2R + G: Within the limit.

    592.5

    550 to 70011.2.2

  • Risers in one flight: Within the limit.

    16

    2 to 1811.2.2(1)(a)

  • Total going: For information.

    3750 mm

    15 goings

  • Pitch: For information.

    34.4°

    from level

This checks the deemed-to-satisfy dimensions for houses (Class 1 and Class 10 buildings) in NCC 2022. State variations and your approved plans come first, and your certifier has the final say.

What the code asks for

  • Risers are 115 to 190 mm and goings are 240 to 355 mm. Twice the riser plus the going (2R + G) lands between 550 and 700. Table 11.2.2a
  • A flight has at least 2 risers and no more than 18. 11.2.2(1)(a)
  • Risers and goings stay the same through a flight. Next-door steps can differ by up to 5 mm, and the biggest and smallest in the flight by up to 10 mm. 11.2.2(1)(c)
  • Open risers are allowed, but no gap can let a 125 mm sphere through. 11.2.2(1)(d)
  • Spiral stairs use risers of 140 to 220 mm, goings of 210 to 370 mm and 2R + G from 590 to 680. Table 11.2.2a
  • A stair that only serves an attic, storeroom or similar room that is not used daily can use risers of 130 to 225 mm, goings of 215 to 355 mm and 2R + G from 540 to 700. Table 11.2.2b
  • Winders can replace a quarter landing (up to 3 winders) or a half landing (up to 6). 11.2.2(3)
  • Keep 2000 mm of headroom, measured straight up from the nosing line. 10.3.1(1)(f)
  • Treads need a slip rating of P3 or R10 where they stay dry and P4 or R11 where they get wet. A nosing strip rated P3 (dry) or P4 (wet) does the same job. Table 11.2.4

Source: Part 11.2 of the ABCB Housing Provisions (NCC 2022). The riser, going and 2R + G limits are the same in NCC 2025.

Questions people ask

What is 2R + G?

Twice the riser plus the going. It ties the two numbers together so a stair is neither too steep nor too flat to walk. A 171 mm riser with a 250 mm going gives 592, which sits inside the 550 to 700 range.

How do I work out how many risers I need?

Divide the total rise (finished floor to finished floor) by the riser you would like and round to a whole number. Then divide the rise by that number to get the real riser. The auto setting does this for you and aims for a riser close to 175 mm.

Do these limits apply to units and commercial buildings?

No. These are the limits for houses and their sheds, garages and decks (Class 1 and Class 10 buildings). Apartments and commercial buildings follow Volume One of the code, which has different numbers.